User Manual for Fireproof Rolling Shutter VR60: Maintenance and Optimal Safety

The user manual for the Flema VR60 fireproof rolling shutter is designed to guide users in proper maintenance and safety practices. This guide aims to ensure the optimal functioning and maximum security of your installation while extending its service life. It outlines essential steps for periodic maintenance or replacement of worn parts.

General Safety Instructions

Before any intervention on the rolling shutter, disconnect the main control box to prevent accidental operation. Components under tension, such as springs or cables, should only be handled by qualified mechanics to avoid potential hazards.

Regular Maintenance

Regular maintenance is essential to guarantee the reliability and safety of your VR60 fireproof rolling shutter. Key maintenance steps include:

  • After installation: grease the guides, bearings, and joints.
  • Every 3 months: complete visual inspection.
  • Every 6 months: check wear on side joints and curtain slats, clean lamellas, and grease key points.
  • Every 12 months: full inspection by a qualified mechanic.
  • Every 2 years: replace the 24V backup batteries to ensure emergency closure.

Usage Tips and Cleaning

Use PTFE or SAE20 grease for lubrication. Clean with mild soap and water, avoiding high-pressure jets or abrasive products that could damage components.